Please note, some Hexing HXE130s and HXP100DII meters, on internal hexing modem and hexing IDIS Concentrator, doesn't want you to log in to the meter, so then you need to check this tick box:

it looks like the DC or modem already log in to them, and then if we do too, it messes up the permissions
At first we found that with xxx's HXE130, now we found it on yyy's  HXP100DII through the IDIS concentrator.
(the way we managed to figure that out is with a bridge to the Hexing HES, that Gift from Hexing helped me with.
I had to go in to Hexing, and sit there in a room with Gift, and get it up and going)
the way it goes wrong, that seems to indicate this problem, is that when we try to GET the serial number of the meter, it fails
C0 01 C1 00 01 00 00 60 01 00 FF 02 00
returns
C4 01 41 01 0B
instead of 
C4 01 41 00 0A 0B 31 34 34 36 31 36 38 34 31 39 34


Tags: addhexing
Avatar

sdg.matiaan
2023-08-03 15:53

 when you select the meter, pls define the following 3 attributes: (Edit->Attributes)
AKey   (should be set up as D0D1D2D3D4D5D6D7D8D9DADBDCDDDEDF)
Ekey    (should be set up as 000102030405060708090A0B0C0D0E0F)
glo-encrypt   (should be set up as     true  )
click on New Attribute Category
then enter DLMS and Save
then go to Edit->Attributes again
and click Setup Attributes again
click add_attribute_type
next to Attribute Name type AKey
for Type, select freeform
click Save
Then go  Edit->Attributes
again
click Setup Attributes again
repeat for EKey
then repeat agajn for glo-encrypt
then go Edit->Attributes again
then enter the values you want, i.e.
D0D1D2D3D4D5D6D7D8D9DADBDCDDDEDF
000102030405060708090A0B0C0D0E0F
true