Landis & Gyr E460 three phase meter support

Avatar

sdg.marinusvz
2023-07-20 11:51
Last Edited 2023-07-20 15:40

Please note, that to support the STS meters, you have to add the meter with a serial number of 11 digits.


Although you add the ZMD and E460 meters both as a Landis & Gyr DLMS meter, the OBIS codes, DLMS login mechanisms etc. are different, so a core way we know which methodology to use, is to look at the length of the serial number entered.

ZMDs must be 8 or 13 digits, and E460s must be 11 digits, regardless of how many phases it uses.


Tags: addlandis & gyr