landis and gyr zmd to riecktron modem pinout and setup

Avatar

sdg.matiaan
2021-03-15 07:11
Last Edited 2023-06-09 15:43

You can make a RS485 connection to the Meter Also.

By using the tested Cable on a B4, P42 and a P32 Modem module.

So the old 2G modem will work as a communications module to connect a LTE/4G modem to.

Here is the wiring for a M2M/Riecktron Modem

NOTE:

The Text message for the M2M Modem on the RS485 connector is:



APN:apnNAME

IP2:SERVER.PNPSCADA.COM

PORT2:13000

Mode2:client

INT2:30

IDX2:2

BAUD2:9600

FRAME2:8N1

RESET



09-06-2023


Tags: landis and gyr zmdlandis & gyrriecktronrs485 communication


Tags: landis and gyr zmdlandis & gyrriecktronrs485 communication
Avatar

remtechco
2021-10-04 11:37

Another thing to add to the post above:

Sometimes it works better when you load it as a DLMS meter (as above), sometimes it might work better when you load it as a L&G IEC meter. (Loading it as an IEC meter you don't need a multidrop, just the serial number). This is unfortunately dependent on the firmware on the meter, so you might have to deal with this on a case-by-case approach.

Avatar

sdg.matiaan
2023-03-23 10:59
Last Edited 2023-03-23 11:01

Pinout to normal RS232 DB9:

remember pin 2 o the RJ11 goes to pin 3 on the DB9
and pin 5 to 2