Temporary Fix - Wasion Meter firmware issue

Avatar

sdg.sean
2018-11-07 13:50

There is a bug in some Wasion meter firmware where the profile memory 'fills up' and profile recording stops. If they read profile fine, but the profile just stops at one place, that would be that error. Go and check if it has stopped. If so, it is a Faulty Meter. A workaround/temporary fix for this would be the following; 
Go to:
  • Edit | Advanced Meter Details
  • (Close to the bottom) select Fix Profile Firmware Error
  • Submit
PLEASE NOTE: This checkbox gets it starting again, at the price of deleting all the profile on the meter.