Iskra MT174 Setup

Avatar

sdg.matiaan
2024-03-25 10:16
Last Edited 2024-03-25 10:17

please make sure the following is logged in IEC readout (don't log more than 30 codes):
(these all have '1-0:' in front)
0.9.1*255 - date
0.9.2*255 - time
0.0.0*255 - serial
1.8.0*255 - current main total (check total)
2.8.0*255 - if solar on tariff (check total)
5.8.0*255 - if reactive on tariff (check total)
6.8.0*255 - if full 4 quadrant metering (check total)
7.8.0*255 - if full 4 quadrant metering (check total)
8.8.0*255 - if full 4 quadrant metering (check total)
1.8.0*0 - main total start of month (billing total), you probably have to tick a check to 'stack' these values under 1.8.0*255
2.8.0*0 - solar total start of month (billing total)
5.8.0*0 - reactive total start of month (billing total)
32.7.0 - red voltage
52.7.0 - white voltage
72.7.0 - blue voltage
31.7.0 - red current
51.7.0 - white current
71.7.0 - blue current
33.7.0 - red current angle
53.7.0 - white current angle
73.7.0 - blue current angle

please make sure the following is enabled for profile (don't log more than 6 channels):
1.5 - main consumption (average kW)
5.5 - if demand (average kvarh)
2.5 - if solar (average kW)
6.5 - if 4 quadrant metering (average kvarh)
7.5 - if 4 quadrant metering (average kvarh)
8.5 - if 4 quadrant metering (average kvarh)