CLOU CL710K

Avatar

sdg.matiaan
2021-06-07 06:28

K1, K22, maybe also C1 (not STS). Not K11 (split prepaid) since no modem and no rs485

Catalog

Meter View's login is Administrator and password is 000000.
It has to be registered (code exchange) to work.

APN Setup:


Setup of modem in Active Mode and the server's IP en port


If you're connecting as a generic APN modem, that is where you set up the modem's receiving port


Supposed to be HDLC multidrop, but I haven't gotten it to work yet


Tags: clou
Avatar

sdg.matiaan
2021-06-07 14:33

CLOU HDLC multidrop must be in range 128-254.
In meter, first byte 01h second byte 00h - 7Eh.
Multidrop in HES must be set to HDLC Device address in meter first byte times 128 plus second byte.

Please log in to post a comment