sdg.matiaan
2020-10-16 11:20
You can add a AD120 as a modbus meter:
Register Address 40960
Format: 4 Byte Integer
sdg.marinusvz
2020-10-16 10:05
Are you sure? From my analysis of the register spreadsheet, it looks like register 40960 (decimal. HEX is A000H) on the third sheet, - note it is a kWh register.
And based on the fact the next register is 2 places on, it looks like a 4 byte integer. (2 modbus registers). Therefore the Format is in my opinion a 4 Byte integer. Not sure of the endian format of that, you must play around with that and see what you get.
Also, the scaling seems to be a ratio of 1/100, so you have to set the multiplier in Meter Details to 0.01 or 1 / 100, I think.
corriee
2023-02-09 14:33
Last Edited 2023-07-01 12:41
2023
Honeywell AD120
Modbus Address: xxxRegester to: 000Register to: 4 Byte Integer (Big Endian)
corriee
2023-07-01 12:39