Here is a list of the most common [URL=\"http://wiki.pnpscada.com/farticle.jsp?article=1151"]RS232 setup for meters in PnPScada.\
\

    \
    \
  • 8N1 - 8 databits, no parity, 1 stop bit\
    \
  • 7E1 - 7 databits, even parity, 1 stop bit\
    \

Note

It is possible to emulate 7E1 over a line (or modem) that is 8N1.\
\
For multidrop reasons, the [URL=\"http://wiki.pnpscada.com/farticle.jsp?article=1145"]Communication Device for a 7E1 meter, should still be set up as 8N1, if applicable.\
\
\
\
[TABLE=\"class: grid, width: 500\"]\
\\
\Meter\
\BAUD\
\Frame\
\
\
\\
\EDMI Atlas\
\9600\
\8N1\
\
\
\\
\EDMI Genius\
\9600\
\8N1\
\
\
\\
\Elster A100C Irda\
\9600\
\7E1\
\
\
\\
\Elster A1140\
\9600\
\7E1\
\
\
\\
\Elster A140\
\9600\
\7E1\
\
\
\\
\Elster A1700\
\9600\
\7E1\
\
\
\\
\Elster A220\
\9600\
\7E1\
\
\
\\
\Elster AS1440\
\9600\
\8N1\
\
\
\\
\Elster AS230\
\9600\
\8N1\
\
\
\\
\Enermax\
\9600\
\7E1\
\
\
\\
\Enermax Plus\
\9600\
\7E1\
\
\
\\
\Etron/TimeSmart\
\9600\
\8N1\
\
\
\\
\Janitza UMG103\
\9600\
\8N1\
\
\
\\
\Janitza UMG604\
\9600\
\8N1\
\
\
\\
\KoCoS IrDA\
\9600\
\8N1\
\
\
\\
\Landis & Gyr\
\9600\
\8N1\
\
\
\\
\Oil Advantage\
\9600\
\8N1\
\
\
\\
\PRI Premier\
\2400\
\8N1\
\
\
\\
\Wavenis\
\9600\
\8N1\
\
\
\