Advanced Settings Meter PNPSCADA

To specify a different Automatic Read Interval than daily (at midnight) or every X minutes, select custom, and enter one of the following options:\
daily OR weekly OR monthly OR once\
\
This will by default read in midnight morning, the first day of the month/week(Monday).\
If you want to change the time or day, enter a colon after the word, and additional data as follows:\
For daily:\
time in the format 23:00 (11'o'clock at night), for example: daily:23:00\
If you want to read in multiple times a day, specify more times seperated by a comma, for example:daily:00:00,08:00\
For weekly:\
day in the format Mo/Tu/We/Th/Fr/Sa/Su, followed by time, for example: weekly:Tu00:00\
If you want to read in multiple times a week, specify more times seperated by a comma, for example:weekly:Su12:00,We00:00,Fr08:00\
For monthly:\
day of the month offset in the format +00 for the first day, +01 for the second day, -01 for the last day, -02 for the second last day, etc.\
Follow this by a 'day type' identifier, being 2 spaces (' ') for a normal day, or the day of the week for a week day (Mo/Tu/We/Th/Fr/Sa/Su), followed by the time.\
For example: monthly:+02 01:00 (Please Use two spaces between the 02 and the 01) \
(this read it in up to the third day of the month, 1'o'clock in the morning)\
monthly:-02Th08:00,+00We06:00 (this read it in up to the second last Thursday of the month at 8am, or the first Wednesday of the month at 6am, whichever is most recent)\
For once:\
This was mainly added for support of SAP and other master systems wanting to use Plug and Play Scada from other scheduling systems.\
Follow this by the date and time in format YYYY-MM-DD HH:MM:SS of up to when you want to call in the meter. Multiple times can be specified delimited by comma. \
Please note that the shortest period for calling in using any SDG SIM card is midnight morning of the same day.\
\
To function correctly, the Profile Sample Period Length must be the same as it is programmed in the meter. Please make sure the setting in Plug and Play Scada is the same as the setting in the meter. Plug and Play Scada supports profile periods of a minute and up. It must be smaller or equal to a day, and it must really be divisible into a day, otherwise you'll get strange results. For best results, we advise making it divisible into an hour, e.g. common periods used are 1 minute, 5 minutes, 15 minutes or 30 minutes.\
\